7. Technical data
Item No.
FURM50000
Conforms to
EN 14604: 2005+corr:2008
Smoke detection
Optical using (scattered light principle)
Power supply
4.5 V DC, 3 AA alkaline batteries
Replacement batteries: ABUS recommend
Duracell MN1500, Eveready Energizer E91
“Low battery” error message
< 3.2 V
“Low battery” warning
Approx. 30 days before discharge
Operational battery life
Approx. 2 years
Dimensions (diameter x height)
122 mm x 50 mm (Ø x H)
Environmental conditions
Only approved for indoor use
Operating temperature
-10 °C - +65 °C
Max. humidity
Average relative humidity approx. 75% non-
condensing
Environmental class
II (EN 50131-1 + A1:2009)
Protection class
IP 20
Security level
2 (EN 50131-1 + A1:2009)
Radio frequency
868.6625 MHz
Wireless transmission power
10mW
Wireless range
Approx. 30m indoors (depending on
environmental factors)
HF immunity
10 V/m (EN 50130-4:2011)
Signals
Acoustic (Piezo) and visual (LED)
Volume
Min. 85 dB(A) @ 3 m
Sound frequency
2.7 kHz
Optical display
LED
Tamper surveillance
No
Supervision monitoring
Yes approx. every 4 minutes
Weight
227,8 g net